Three-Level NPC and ANPC Power Module Selection

NPC, T-type and ANPC phase legs all produce three output levels, but they differ in device count, loss distribution and layout demands. This guide compares them and shows how to match voltage class, chip technology and package.

Three-level inverters are a common choice for solar inverters, energy storage PCS and UPS systems. The harder question is which three-level phase leg to build, and which power module to put in it. This guide compares NPC, T-type (TNPC) and ANPC topologies, then walks through a selection checklist. At the end, it maps the options to modules from HIITIO Semiconductor, a manufacturer of IGBT, SiC and hybrid power modules and gate drivers.

Why Choose a Three-Level Phase Leg?

According to Semikron Danfoss Application Note AN 11-001, three-level topologies lower the current THD, which reduces the filtering effort. NPC and ANPC legs can also use devices rated below the full DC-link voltage, and the lower-blocking devices tend to have lower losses.

The trade-offs are real:

  • More devices. A 2L phase leg has 4 semiconductors; an NPC leg has 10, a TNPC leg 8 and an ANPC leg 12.
  • More gate drivers. Auxiliary power and control effort grow with the number of IGBTs.
  • More complex switching. The application note counts 16 switching states for NPC and TNPC and 64 for ANPC, with several that are destructive.

NPC, T-Type and ANPC Compared

Table 1 summarizes the differences. Device counts, voltage limits and switching states come from the Semikron Danfoss note; the loss-distribution row reflects the literature discussed in the next section.

Table 1. Three-level topologies at a glance

Item3L NPC3L TNPC (T-type)3L ANPC
Semiconductors per leg10 (4 IGBT, 4 FWD, 2 clamp diodes)8 (4 IGBT, 4 FWD)12 (6 IGBT, 6 FWD)
Device blocking voltageBelow DC-link voltageOuter switches see full DC link; inner switches halfBelow DC-link voltage
Max DC link with 650 V / 1200 V / 1700 V devices800 / 1500 / 2400 V400 / 800 / 1200 V800 / 1500 / 2400 V
Switching states161664
Switching restrictionsSome states destructiveFewer restrictionsDifferent pattern required
Loss distributionFixed, unevenFixedControllable through zero-state choice

In short, NPC is the mature, lower-cost option; T-type reduces part count and conduction paths; and ANPC adds control freedom at the price of two more active switches per leg.

Loss Distribution Is the Real ANPC Argument

In a conventional NPC leg, loss is not shared evenly. A 2021 IEEE APEC paper from Aalborg and Kiel universities notes that neutral-point-clamped converters suffer from unbalanced thermal stress, so some devices run hotter than others. In ANPC, the clamp diodes are replaced by switches, which allows alternative zero states.

An onsemi application note (AND90322/D) quantifies this for one design example: a 150 kVA inverter at 25 kHz built with SiC cascode FETs. Semiconductor loss fell by up to 34% for ANPC with its PWM4 strategy compared with NPC. This is one worked example with a specific device set, not a general rule, and the note itself says ANPC costs more. Another detail is useful for hybrid designs. In that example, IGBTs in the clamp positions matched an all-FET build only in inverter mode.

Commutation Loops and Module Layout

Layout matters as much as topology. The Semikron Danfoss note explains that ANPC comes in two modulation variants:

  • HF/LF: the input stage (T1, T4, T5, T6) switches at the PWM frequency and the output stage (T2, T3) at line frequency. It uses short commutation paths for most events, so it can be built from standard 2L modules.
  • LF/HF: the reverse allocation. It involves long commutation paths in the switching stage, so all devices should sit inside one housing with optimized stray inductance. It reduces the number of fast switches, which helps when those switches are SiC.

For NPC and TNPC, the note advises dedicated 3L modules, because building them from 2L modules creates long commutation loops and high voltage overshoot.

Commercial examples show the direction of travel. Infineon’s EasyPACK 2B hybrid ANPC module pairs a CoolSiC MOSFET with a TRENCHSTOP IGBT and supports switching up to 48 kHz, according to the company. A related variant, the F3L11MR12W2M1_B74 combines SiC MOSFETs with IGBT7 and offers full 1500 VDC capability using 1200 V switches.

Selection Checklist

  1. Start from the DC-link voltage. Use Table 1 to find the voltage class: 1200 V devices in NPC or ANPC reach 1500 VDC, while T-type with 1200 V devices is limited to 800 VDC. Leave margin for switching overshoot.
  2. Choose the chip technology by switching frequency. IGBTs suit medium-to-low frequency, high-power designs; SiC is preferred for high-frequency, high-efficiency ones, as HIITIO’s photovoltaic solution page puts it. Hybrid modules sit in between.
  3. Calculate loss per switch position. Positions carry different stress in each topology, so size them individually. Semikron Danfoss offers its SemiSel tool, and the onsemi note provides closed-form equations.
  4. Check current and overload per position. Outer and inner devices in a T-type leg are rated differently.
  5. Review the package and stray inductance. Prefer a purpose-built 3L module over bus-bar assemblies of 2L modules.
  6. Plan the gate drive. Turn off outer IGBTs first and inner IGBTs 1–3 µs later; a desaturation event leaves at most 10 µs to act, according to the Semikron Danfoss note. Drivers should support soft shutdown, UVLO and active clamping.

HIITIO Modules to Evaluate

Table 2 lists three-level modules from the HIITIO catalog. The DC-link column applies the Semikron Danfoss rule of thumb and is a starting point, not a derating guarantee. Always confirm against the datasheet.

Table 2. HIITIO three-level modules

ModuleChip typeRatingPackageTopologyDC-link guideline
HCG375FL065E3RCIGBT650 V / 375 AEasy 3BNPC (I-type)~800 V
HCG400FL120E3RAIGBT1200 V / 400 AEasy 3BNPC (I-type)~1500 V
HCG500FL120E3TMIGBT1200 V / 500 AEasy 3BT-type NPC (per datasheet)~800 V
HCG600FL120E3T1Hybrid1200 V / 600 AEasy 3BNPC three-level~1500 V
HCH10FA120E2C1SiC/IGBT hybrid1200 V / 100 AEasy 2BANPC~1500 V

The HCG500FL120E3TM has the most detailed datasheet. It uses 1200 V trench-gate/field-stop IGBTs in the outer positions (T1/T4) and 650 V IGBTs in the inner positions (T2/T3). VCE(sat) is 1.81 V at 500 A and 25 °C for the outer IGBTs, and 1.58 V at 450 A for the inner ones. Maximum junction temperature is 175 °C, stray inductance is 25 nH, and the module uses a copper baseplate with an optional integrated DC capacitor. The datasheet lists PCS, UPS, solar and APF/SVG applications.

The HCG400FL120E3RA is a 1200 V, 400 A I-type NPC module with an Al₂O₃ substrate and copper baseplate, rated for up to 175 °C. For higher switching frequency, the hybrid HCH10FA120E2C1 combines 1200 V SiC MOSFET and IGBT chips for three-level solar and energy storage use. HIITIO’s wind power solution page states that its half-bridge and chopper modules suit NPC and ANPC multilevel converters.

On the drive side, HIITIO’s Plug-and-Play Gate Driver lists support for multi-level applications, soft shutdown, UVLO and active clamping for modules up to 1700 V. The gate driver category also cites a 1.7 MW air-cooled ANPC/NPC three-level power stack. For a broader supplier view, see the HIITIO guide to the top 10 IGBT gate driver suppliers, and for assembly considerations the article on grease vs phase change thermal interface materials.

Ready to Select Your Three-Level Power Module?

Whether you are building a 1500 V solar inverter, an energy storage PCS or a UPS, the right NPC, T-type or ANPC module depends on your DC-link voltage, switching frequency and thermal budget. HIITIO’s engineering team can help you shortlist modules from the IGBT, SiC/Si hybrid and SiC ranges, and pair them with a matching gate driver. Share your topology, bus voltage, power level and cooling method, and we will recommend candidates with datasheets for your own loss and thermal calculations. Visit hiitiosemi.com to request datasheets or a custom power module solution.

FAQ

Is ANPC always better than NPC?

No. ANPC offers better control over loss distribution and, in some designs, higher efficiency, but it adds two active switches and two gate drivers per leg and needs a more complex switching pattern. For lower-frequency designs where NPC thermal margins are comfortable, NPC can be the more economical choice.

When should I use a T-type leg instead of NPC?

T-type uses fewer semiconductors and has fewer switching restrictions, but its outer devices must block the full DC-link voltage. With 1200 V devices the limit is 800 VDC, against 1500 VDC for NPC or ANPC. It fits lower-voltage bus designs.

Can I build a three-level inverter from standard half-bridge modules?

Only ANPC HF/LF is practical, according to Semikron Danfoss, because its fast commutations stay inside each half-bridge. NPC and TNPC built from 2L modules create long commutation paths and high overshoot, so dedicated 3L modules are recommended.

Does HIITIO offer ANPC modules?

HIITIO lists the HCH10FA120E2C1, a 1200 V, 100 A hybrid three-level module, under ANPC in its PV solution. It also lists NPC and T-type modules in 650 V and 1200 V classes (see Table 2). For other ratings or voltage classes, contact the HIITIO team.

Should the clamp switches use SiC or IGBT?

It depends on the operating mode and modulation. In the onsemi example, IGBTs in the clamp positions matched an all-FET design only in inverter mode, and rectifier operation favored FETs. Model your own duty cycle before deciding.

How Can We Help?

Get a Custom Power Module Solution

Tell us your project requirements, and our engineering team will provide tailored recommendations within 24 hours.